| 标称截面 | 电外 | 电缆近似重量 | 20℃导体最大直流电阻 | Cayingaity | |||||
| 在空气中 intheair | 直埋土壤中 Underground | ||||||||
| mm² | mm | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 3×35 | 77.3 | 6262 | 5621 | 0.524 | 0.868 | 171 | 182 | 160 | 125 |
| 3×50 | 81.1 | 6963 | 6098 | 0.387 | 0.641 | 205 | 160 | 190 | 145 |
| 3×70 | 85.2 | 10009 | 8752 | 0.268 | 0.443 | 251 | 194 | 230 | 180 |
| 3x95 | 89.2 | 11346 | 9589 | 0.193 | 0.320 | 302 | 234 | 275 | 215 |
| 3x120 | 92.0 | 12395 | 10192 | 0.153 | 0.253 | 353 | 274 | 315 | 245 |
| 3x150 | 95.9 | 13748 | 11031 | 0.124 | 0.206 | 399 | 308 | 355 | 275 |
| 3x185 | 99.9 | 15349 | 11937 | 0.0991 | 0.164 | 456 | 353 | 400 | 310 |
| 3×240 | 105.5 | 17707 | 13248 | 0.0754 | 0.125 | 530 | 410 | 460 | 360 |
| 3x300 | 111.0 | 20233 | 14612 | 0.0601 | 0.100 | 610 | 479 | 520 | 410 |
| 3x400 | 117.5 | 23472 | 16437 | 0.0470 | 0.0778 | 701 | 553 | 590 | 465 |
21/35kV三芯交联聚乙烯绝缘钢丝铠装聚氯乙烯/聚乙烯护套电力电缆(YIV32YJLV32YIY33YJLY3:
21/35kV3 CoresXLPE Insulated Steelwire Armoured PVC/PESheathed Power Cable.
| 标称截面 | 电 | 电缆近似重量 | 20℃导体最大直流电阻 | Ccayigacity | |||||
| 在空气中 Intheair | 直埋土壤中 Underground | ||||||||
| mm² | mm | Cu | Al | Cu | AL | Cu | Al | Cu | Al |
| 3×35 | 82.6 | 9481 | 8841 | 0.524 | 0.868 | 171 | 182 | 160 | 125 |
| 3×50 | 85.2 | 10253 | 9388 | 0.387 | 0.641 | 205 | 160 | 190 | 145 |
| 3×70 | 89.3 | 12753 | 11495 | 0.268 | 0.443 | 251 | 194 | 230 | 180 |
| 3×95 | 93.3 | 14249 | 12493 | 0.193 | 0.320 | 302 | 234 | 275 | 215 |
| 3x120 | 96.3 | 15397 | 13194 | 0.153 | 0.253 | 353 | 274 | 315 | 245 |
| 3x150 | 100.0 | 16870 | 14153 | 0.124 | 0.206 | 399 | 308 | 355 | 275 |
| 3x185 | 104.0 | 18624 | 15212 | 0.0991 | 0.164 | 456 | 353 | 400 | 310 |
| 3×240 | 109.6 | 21165 | 16706 | 0.0754 | 0.125 | 530 | 410 | 460 | 360 |
| 3x300 | 114.9 | 23823 | 18202 | 0.0601 | 0.100 | 610 | 479 | 520 | 410 |
| 3x400 | 121.6 | 27339 | 20304 | 0.0470 | 0.0778 | 701 | 553 | 590 | 465 |
26/35kV单芯交联聚乙烯绝缘聚氯乙烯/聚乙烯护套电力电缆
26/35kV1-CoreXLPEInsulatedPVC/PESheathedPowerCable.
| AP | |||||||||
| mm² | mm | Cu | AL | Cu | AL | Cu | Al | Cu | Al |
| 1×35 | 37.0 | 1497 | 1285 | 0.524 | 0.868 | 217 | 159 | 191 | 137 |
| 1×50 | 38.3 | 1683 | 1396 | 0.387 | 0.641 | 285 | 217 | 225 | 175 |
| 1×70 | 40.0 | 1954 | 1538 | 0.268 | 0.443 | 348 | 274 | 275 | 215 |
| 1×95 | 41.9 | 2294 | 1711 | 0.193 | 0.320 | 428 | 331 | 335 | 260 |
| 1×120 | 43.2 | 2576 | 1846 | 0.153 | 0.253 | 496 | 382 | 380 | 295 |
| 1×150 | 44.9 | 2925 | 2024 | 0.124 | 0.206 | 559 | 433 | 425 | 330 |
| 1×185 | 46.8 | 3359 | 2228 | 0.0991 | 0.164 | 644 | 496 | 485 | 375 |
| 1×240 | 49.1 | 3974 | 2496 | 0.0754 | 0.125 | 758 | 593 | 565 | 438 |
| 1x300 | 51.6 | 4664 | 2800 | 0.0601 | 0.100 | 866 | 673 | 635 | 495 |
| 1x400 | 54.5 | 5566 | 3234 | 0.0470 | 0.0778 | 1015 | 792 | 730 | 570 |
| 1x500 | 58.1 | 6739 | 3708 | 0.0366 | 0.0605 | 1174 | 923 | 830 | 655 |
| 1×630 | 61.7 | 8228 | 4265 | 0.0283 | 0.0469 | 1368 | 1083 | 950 | 755 |
26/35kV三芯交联聚乙烯绝缘聚氯乙烯/聚乙烯护套电力电缆 (YJV YJLV YJY YJLY)
26/35kV3CoresXLPE Insulated PVC/PESheathed Power Cable.
| 标称截面 | 电线外径 | 电缆近似重量 | 20℃导体最大直流电阻 | Cayingracity | |||||
| 在空气中 Intheair | 直埋土壤中 Underground | ||||||||
| mm² | mm | Cu | Al | Cu | AL | Cu | Al | Cu | Al |
| 3×35 | 76.7 | 4910 | 4270 | 0.524 | 0.868 | 171 | 131 | 160 | 125 |
| 3×50 | 79.3 | 5544 | 4679 | 0.387 | 0.641 | 205 | 160 | 190 | 145 |
| 3×70 | 83.3 | 6485 | 5228 | 0.268 | 0.443 | 251 | 194 | 230 | 180 |
| 3×95 | 87.0 | 7537 | 5781 | 0.193 | 0.320 | 302 | 234 | 275 | 215 |
| 3x120 | 90.0 | 8487 | 6284 | 0.153 | 0.253 | 348 | 268 | 315 | 245 |
| 3x150 | 93.4 | 9570 | 6853 | 0.124 | 0.206 | 393 | 308 | 355 | 275 |
| 3x185 | 97.3 | 10911 | 7499 | 0.0991 | 0.164 | 445 | 348 | 400 | 310 |
| 3×240 | 102.7 | 12916 | 8457 | 0.0754 | 0.125 | 519 | 405 | 460 | 360 |
| 3x300 | 108.0 | 15081 | 9460 | 0.0601 | 0.100 | 599 | 467 | 520 | 410 |
| 3x400 | 114.2 | 18060 | 11025 | 0.0470 | 0.0778 | 684 | 536 | 590 | 465 |
26/35kV单芯交联聚乙烯绝缘非磁性金属带铠装聚氯乙烯/聚乙烯护套电力电缆 (YJV62YJLV62 YJY63YJLY63) 26/35kV1 Core XLPE Insulated Stainless Steel Tape Armoured PVC/PE Sheathed Power Cable.
| AP | |||||||||
| Intheair | Underground | ||||||||
| mm² | mm | Cu | AL | Cu | AL | Cu | AL | Cu | Al |
| 1×35 | 41.8 | 2341 | 2129 | 0.524 | 0.868 | 217 | 159 | 191 | 137 |
| 1×50 | 42.9 | 2534 | 2247 | 0.387 | 0.641 | 271 | 202 | 213 | 165 |
| 1×70 | 44.8 | 2864 | 2447 | 0.268 | 0.443 | 336 | 251 | 260 | 202 |
| 1×95 | 46.7 | 3244 | 2661 | 0.193 | 0.320 | 405 | 303 | 310 | 241 |
| 1×120 | 48.2 | 3579 | 2849 | 0.153 | 0.253 | 465 | 347 | 351 | 273 |
| 1×150 | 49.9 | 3965 | 3064 | 0.124 | 0.206 | 526 | 393 | 393 | 305 |
| 1x185 | 51.6 | 4417 | 3286 | 0.0991 | 0.164 | 598 | 448 | 442 | 345 |
| 1×240 | 54.3 | 5135 | 3657 | 0.0754 | 0.125 | 701 | 513 | 510 | 398 |
| 1x300 | 56.8 | 5881 | 4018 | 0.0601 | 0.100 | 798 | 597 | 572 | 448 |
| 1×400 | 59.9 | 6879 | 4547 | 0.0470 | 0.0778 | 922 | 695 | 649 | 512 |
| 1×500 | 63.5 | 8136 | 5105 | 0.0366 | 0.0605 | 1054 | 794 | 730 | 576 |
| 1×630 | 67.3 | 9741 | 5778 | 0.0283 | 0.0469 | 1242 | 939 | 845 | 671 |
26/35kV单芯交联聚乙烯绝缘非磁性金属丝铠装聚氯乙烯/聚乙烯护套电力电缆(YIV72YJLV72 (YJV72YJLV72YJY73YJLY73)
26/35kV1 Core XLPE Insulated Stainless Steel Wire Ammoured PVC/PE Sheathed Power Cable.
| AP | |||||||||
| Intheair | Underground | ||||||||
| mm² | mm | Cu | Al | Cu | AL | Cu | AL | Cu | AL |
| 1×35 | 45.8 | 2955 | 2743 | 0.524 | 0.868 | 217 | 159 | 191 | 137 |
| 1×50 | 47.1 | 3178 | 2891 | 0.387 | 0.641 | 271 | 202 | 213 | 165 |
| 1×70 | 48.8 | 3513 | 3096 | 0.268 | 0.443 | 336 | 251 | 260 | 202 |
| 1x95 | 50.7 | 3920 | 3338 | 0.193 | 0.320 | 405 | 303 | 310 | 241 |
| 1×120 | 52.2 | 4283 | 3553 | 0.153 | 0.253 | 465 | 347 | 351 | 273 |
| 1×150 | 53.9 | 4699 | 3799 | 0.124 | 0.206 | 526 | 393 | 393 | 305 |
| 1x185 | 55.6 | 5176 | 4044 | 0.0991 | 0.164 | 598 | 448 | 442 | 345 |
| 1×240 | 58.3 | 5934 | 4456 | 0.0754 | 0.125 | 701 | 513 | 510 | 398 |
| 1x300 | 60.8 | 6724 | 4860 | 0.0601 | 0.100 | 798 | 597 | 572 | 448 |
| 1×400 | 63.9 | 7780 | 5448 | 0.0470 | 0.0778 | 922 | 695 | 649 | 512 |
| 1×500 | 67.5 | 9089 | 6058 | 0.0366 | 0.0605 | 1054 | 794 | 730 | 576 |
| 1×630 | 71.3 | 10769 | 6806 | 0.0283 | 0.0469 | 1242 | 939 | 845 | 671 |
| 标称截面 | 电外 | 电缆近似重量 | 20℃导体最大直流电阻 | Cayingacity | |||||
| 在空气中 Intheair | 直埋土壤中 Underground | ||||||||
| mm² | mm | Cu | Al | Cu | Al | Cu | Al | Cu | Al |
| 3×35 | 84.3 | 7685 | 7045 | 0.524 | 0.868 | 171 | 182 | 160 | 125 |
| 3×50 | 86.9 | 8408 | 7543 | 0.387 | 0.641 | 205 | 160 | 190 | 145 |
| 3×70 | 90.9 | 11118 | 9861 | 0.268 | 0.443 | 251 | 194 | 230 | 180 |
| 3x95 | 94.8 | 12460 | 10703 | 0.193 | 0.320 | 302 | 234 | 275 | 215 |
| 3x120 | 97.8 | 13584 | 11381 | 0.153 | 0.253 | 353 | 274 | 315 | 245 |
| 3x150 | 101.6 | 14981 | 12264 | 0.124 | 0.206 | 399 | 308 | 355 | 275 |
| 3x185 | 105.7 | 16629 | 13216 | 0.0991 | 0.164 | 456 | 353 | 400 | 310 |
| 3×240 | 111.3 | 19049 | 14590 | 0.0754 | 0.125 | 530 | 410 | 460 | 360 |
| 3x300 | 116.8 | 21639 | 16018 | 0.0601 | 0.100 | 610 | 479 | 520 | 410 |
| 3x400 | 123.2 | 24952 | 17916 | 0.0470 | 0.0778 | 701 | 553 | 590 | 465 |
26/35kV三芯交联聚乙烯绝缘钢丝铠装聚氯乙烯/聚乙烯护套电力电缆
6/35kV3 CoresXLPE Insulated Steel Wire Armored PVC/PESheathed PowerCable.
| AP | |||||||||
| Intheair | Underground | ||||||||
| mm² | mm | Cu | Al | Cu | AL | Cu | Al | Cu | Al |
| 3×35 | 88.4 | 10389 | 9749 | 0.524 | 0.868 | 171 | 182 | 160 | 125 |
| 3×50 | 91.0 | 11179 | 10313 | 0.387 | 0.641 | 205 | 160 | 190 | 145 |
| 3×70 | 95.0 | 14040 | 12783 | 0.268 | 0.443 | 251 | 194 | 230 | 180 |
| 3×95 | 98.9 | 15540 | 13783 | 0.193 | 0.320 | 302 | 234 | 275 | 215 |
| 3x120 | 101.9 | 16781 | 14578 | 0.153 | 0.253 | 353 | 274 | 315 | 245 |
| 3x150 | 105.7 | 18282 | 15565 | 0.124 | 0.206 | 399 | 308 | 355 | 275 |
| 3x185 | 109.8 | 20082 | 16670 | 0.0991 | 0.164 | 456 | 353 | 400 | 310 |
| 3×240 | 115.4 | 22687 | 18228 | 0.0754 | 0.125 | 530 | 410 | 460 | 360 |
| 3x300 | 120.7 | 25405 | 19784 | 0.0601 | 0.100 | 610 | 479 | 520 | 410 |
| 3x400 | 127.3 | 28997 | 21962 | 0.0470 | 0.0778 | 701 | 553 | 590 | 465 |
十、电缆主要技术参数 Main Technical SpecificationsoftheCable
| 标称截面积 Nominalcross sectionalareaof conductor(mm2) | 铜导体 Copper conductor | 铝导体 Aluminiumconductor |
| 25 | 0.727 | 1.20 |
| 35 | 0.524 | 0.868 |
| 50 | 0.387 | 0.641 |
| 70 | 0.268 | 0.443 |
| 95 | 0.193 | 0.32 |
| 120 | 0.153 | 0.253 |
| 150 | 0.124 | 0.206 |
| 185 | 0.0991 | 0.164 |
| 240 | 0.0754 | 0.125 |
| 300 | 0.0601 | 0.1 |
| 400 | 0.047 | 0.0778 |
| 500 | 0.0366 | 0.0605 |
| 630 | 0.0283 | 0.0469 |
电压试验、局部放电试验VoltagetestandPartialdischargetest
| 序号 | 额定电压RatedvoltagekV | |||||||
| 试验项目Testitems | 3.6/6 | 6/10 | 8.7/15 | 12/20 | 18/20 | 21/35 | 26/35 | |
| 1 | 工频交流电压试验 Power frequency A.C.Voltage testkV/5min | 12.2 | 21 | 30.5 | 42 | 63 | 73.5* | (951* |
| 2 | 四小时工频交流电压试验 A-C.Voltage test for4 hours kV | 14.4 | 24 | 34.8 | 48 | 72 | 84 | 104 |
| 3 | 冲击电压试验 Impulse voltage test kv | 60 | 75 | 95 | 125 | 170 | 200 | 250 |
| 4 | 局部放电试验 Partialdischarge testpCMaximumdischargeat 1.73 U。 | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
| *21/35kV和26/35kV电缆工频耐压试验可根据用户要求,按2.5U。×30min或3.5U。×5min进行试验。 The power-frequency Voltage test of cables for rated voltage 21/35kVor26/35kVshall be done upon requestaccording to 2.5U。×30min or3.5U。×5min | ||||||||
| 导体标称截面 Nominalcrosssectional areaofconductor mm² | 导体允许最大短路电流(kA/1s) Maximumallowableshort-circuitcurrentofconductor(kA/1s) | ||
| 铜导体 Copperconductor | 铝导体 Aluminumconductor | ||
| 255 | 3.69 5.15 | 2.42 3.37 | |
| 50 | 7.31 10.2 | 4.79 6.68 | |
| 95 120 | 13.8 17.4 | 9.03 11.4 | |
| 150 185 | 21.7 26.7 | 14.2 17.5 | |
| 240 300 | 34.6 43.1 | 22.6 28.2 | |
| 400 500 630 | 57.4 71.7 88.8 | 37.6 47.0 58.0 | |
| 注:l=l√t lk-tx秒钟短路电流 tk-k秒钟 Notes:Ik=l1√tkIk-Short-circuitcurrent (tk.sec) tk-k.Sec | I-1秒钟短路电流(见上表) l-Short-circuitcurrent(1s) (seeabove) | ||
电容、电感(参考值)Capacitanceand inductanceofcable(referencevalue)
| 导体标称截面 Nominalcconductional mm² | 额定电压RatedvoltagekV | ||||||
| 3.6/6 | 6/60 | 8.7/15 | 12/20 | 18/20 | 21/35 | 26/35 | |
| 每相电容Capacitance/phaseμF/km | |||||||
| 25 | 0.2423 | 0.1922 | 0.1576 | 0.1378 | 0.1163 | 0.1064 | 0.0992 |
| 35 | 0.2684 | 0.2116 | 0.1725 | 0.1502 | 0.1251 | 0.1140 | 0.1061 |
| 50 | 0.3022 | 0.2367 | 0.1917 | 0.1661 | 0.1363 | 0.1239 | 0.1150 |
| 70 | 0.3462 | 0.2693 | 0.2167 | 0.1868 | 0.1508 | 0.1365 | 0.1263 |
| 95 | 0.3875 | 0.2999 | 0.2400 | 0.2060 | 0.1643 | 0.1483 | 0.1368 |
| 120 | 0.4236 | 0.3266 | 0.2603 | 0.2228 | 0.1760 | 0.1584 | 0.1460 |
| 150 | 0.4647 | 0.3570 | 0.2834 | 0.2418 | 0.1893 | 0.1700 | 0.1563 |
| 185 | 0.5059 | 0.3873 | 0.3123 | 0.2656 | 0.2026 | 0.1815 | 0.1665 |
| 240 | 0.5430 | 0.4290 | 0.3439 | 0.2916 | 0.2207 | 0.1972 | 0.1805 |
| 300 | 0.5589 | 0.4706 | 0.3755 | 0.3175 | 0.2387 | 0.2128 | 0.1945 |
| 400 | 0.5940 | 0.5311 | 0.4213 | 0.3551 | 0.2648 | 0.2354 | 0.2146 |
| 500 | 0.6167 | 0.5839 | 0.4613 | 0.3880 | 0.2876 | 0.2551 | 0.2321 |
| 630 | 0.6848 | 0.6481 | 0.5099 | 0.4278 | 0.3151 | 0.2789 | 0.2533 |
| 导体标称截面 Nominalcronductional mm² | 额定电压RatedvoltagekV | ||||||
| 3.6/6 | 6/60 | 8.7/10 | 12/20 | 18/20 | 21/35 | 26/35 | |
| 电感 IndrctancemH/km | |||||||
| 25 | 0.5954 | 0.6143 | 0.6474 | ||||
| 35 | 0.5753 | 0.5932 | 0.6248 | 0.6390 | |||
| 50 | 0.5543 | 0.5711 | 0.6011 | 0.6145 | 0.6501 | 0.6675 | 0.6751 |
| 70 | 0.5357 | 0.5486 | 0.5765 | 0.5919 | 0.6252 | 0.6394 | 0.6467 |
| 95 | 0.5172 | 0.5318 | 0.5608 | 0.5726 | 0.6043 | 0.6180 | 0.6279 |
| 120 | 0.5059 | 0.5197 | 0.5473 | 0.5586 | 0.5891 | 0.6051 | 0.6118 |
| 150 | 0.4949 | 0.5079 | 0.5341 | 0.5449 | 0.5740 | 0.5895 | 0.5959 |
| 185 | 0.4885 | 0.5006 | 0.5252 | 0.5354 | 0.5640 | 0.5760 | 0.5839 |
| 240 | 0.4790 | 0.4890 | 0.5143 | 0.5216 | 0.5487 | 0.5615 | 0.5677 |
| 300 | 0.4749 | 0.4818 | 0.5032 | 0.5102 | 0.5376 | 0.5484 | 0.5540 |
| 400 | 0.4660 | 0.4702 | 0.4927 | 0.4991 | 0.5219 | 0.5343 | 0.5395 |
| 500 | 0.4600 | 0.4619 | 0.4848 | 0.4907 | 0.5128 | 0.5224 | 0.5272 |
| 630 | 0.4547 | 0.4563 | 0.4748 | 0.4827 | 0.5012 | 0.5101 | 0.5161 |
| 注:以上为s=2D时的电感,其中D为电缆外径;s为电缆中心距离。 Note:Inductance Value above isthe Value ats=2D(D-thecable diameter S-distance betweencable centers) | |||||||
| 导体标称截面 Nominalcronductional mm² | 额定电压RatedvoltagekV | ||||||
| 3.6/6 | 6/10 | 8.7/15 | 12/20 | 18/20 | 21/35 | 26/35 | |
| 电感IndrctancemH/km | |||||||
| 25 | 0.3552 | 0.3797 | 0.4061 | 0.4274 | |||
| 35 | 0.3384 | 0.3613 | 0.3862 | 0.4064 | 一 | / | |
| 50 | 0.3211 | 0.3423 | 0.3655 | 0.3845 | 0.4396 | 0.4537 | 0.4679 |
| 70 | 0.3040 | 0.3232 | 0.3445 | 0.3620 | 0.4145 | 0.4286 | 0.4427 |
| 95 | 0.2915 | 0.3092 | 0.3290 | 0.3454 | 0.3956 | 0.4082 | 0.4208 |
| 120 | 0.2826 | 0.2992 | 0.3178 | 0.3392 | 0.3799 | 0.3909 | 0.4019 |
| 150 | 0.2742 | 0.2897 | 0.3071 | 0.3217 | 0.3642 | 0.3752 | 0.3862 |
| 185 | 0.2672 | 0.2817 | 0.3009 | 0.3145 | 0.3485 | 0.3611 | 0.3737 |
| 240 | 0.2608 | 0.2726 | 0.2904 | 0.3030 | 0.3360 | 0.3486 | 0.3611 |
| 300 | 0.2576 | 0.2651 | 0.2817 | 0.2935 | 0.3266 | 0.3776 | 0.3485 |
| 400 | 0.2516 | 0.2564 | 0.2714 | 0.2822 | 0.3014 | 0.3140 | 0.3266 |
| 500 | 0.2480 | 0.2503 | 0.2641 | 0.2742 | |||
| 630 | 0.2421 | 0.2442 | 0.2596 | 0.2661 | 一 | ||
金属屏蔽层的短路电流Shortcircuitcurrentofmechanic-screen
| 导体标称截面 Nominalcronductional mm² | 额定电压RatedvoltagekV | ||||||
| 3.6/6 | 6/10 | 8.7/15 | 12/20 | 18/20 | 21/35 | 26/35 | |
| 短路电流ShortcircuitcurrentA | |||||||
| 25 | 1075 | 1083 | 1094 | 一 | 一 | 一 | |
| 35 | 1074 | 1082 | 1082 | 1096 | 一 | ||
| 50 | 1072 | 1083 | 1091 | 1095 | 1284 | 1286 | 1288 |
| 70 | 1070 | 1079 | 1090 | 1091 | 1281 | 1285 | 1286 |
| 95 | 1069 | 1077 | 1086 | 1272 | 1280 | 1284 | 1283 |
| 120 | 1068 | 1077 | 1266 | 1271 | 1279 | 1280 | 1282 |
| 150 | 1067 | 1076 | 1265 | 1270 | 1278 | 1279 | 1282 |
| 185 | 1064 | 1251 | 1264 | 1267 | 1275 | 1279 | 1279 |
| 240 | 1241 | 1250 | 1262 | 1266 | 1274 | 1276 | 1278 |
| 300 | 1239 | 1246 | 1261 | 1265 | 1271 | 1275 | 1277 |
| 400 | 1240 | 1245 | 1256 | 1260 | 1270 | 1272 | 1274 |
| 500 | 1243 | 1244 | 1253 | 1257 | 1266 | 1272 | 1273 |
| 630 | 1236 | 1238 | 1252 | 1253 | 1265 | 1270 | 1270 |
| 导体标称截面 Nominalcronductional mm² | 额定电压RatedvoltagekV | ||||||
| 3.6/6 | 6/60 | 8.7/15 | 12/20 | 18/20 | 21/35 | 26/35 | |
| 短路电流ShortcircuitcurrentA | |||||||
| 25 | 2958 | 295B | 2958 | 一 | |||
| 35 | 2958 | 2958 | 2958 | 2958 | 一 | 一 | |
| 50 | 295B | 285B | 2958 | 2958 | 3031 | 3031 | 3031 |
| 70 | 2958 | 2958 | 2958 | 2958 | 3031 | 3031 | 3031 |
| 95 | 2958 | 2958 | 2958 | 3031 | 3031 | 3031 | 3031 |
| 120 | 295B | 295B | 3031 | 3031 | 3031 | 3031 | 3031 |
| 150 | 2958 | 295B | 3031 | 3031 | 3031 | 3031 | 3031 |
| 185 | 2958 | 3031 | 3031 | 3031 | 3031 | 3031 | 3031 |
| 240 | 3031 | 3031 | 3031 | 3031 | 3031 | 3031 | 3031 |
| 300 | 3031 | 3031 | 3031 | 3031 | 3031 | 3031 | 3031 |
| 400 | 3031 | 3031 | 3031 | 3031 | 3031 | 3031 | 3031 |
| 500 | 3031 | 3031 | 3031 | 3031 | 1 | 二 | 一 |
| 630 | 3031 | 3031 | 3031 | 3031 | 一 | ||
附录A
载流量计算 AmpacityCalculation
8.1参考载流量
电缆敷设运行条件Installation导体最高工作温度 Max.Rated temperature of the Cable Conductor.....90℃空气温度AirTemperature· 25℃土壤温度 Ground Temperature .25℃
土壤热阻系数Rating factorsfor ground thermal resistive· 1.0℃.m/w
理设深度 Depth..... …0.7m
仅考虑一个回路 Single-Circuit only
单芯电缆为水平敷设,问距为一个电缆外径
Single-core cable is installed in parallel.Adjacent space is equivalentto the diameter of the cable
环境条件对电缆载流量的修正系数 Ratingfactorsofcurrentratingforambientcondition
土壤敷设 Laying in ground 空气敷设Laying inair
| 土壤温度℃ Groundtemperature | 15 | 20 | 25 | 30 | 35 | 40 | 45 |
| 系数 Rating factors | 1.07 | 1.04 | 1.0 | 0.96 | 0.92 | 0.87 | 0.83 |
| 土壤热阻 Ratingfactorsfor groundthermalC.m/w | 1.0 | 1.2 | 1.5 | 2.0 | 2.5 | 3.0 | 3.5 |
| T芯e电缆r | 1.0 | 0.943 | 0.877 | 0.792 | 0.736 | 0.675 | 0.641 |
| 单芯电缆 Single core | 1.0 | 0.934 | 0.850 | 0.748 | 0.692 | 0.635 | 0.598 |
| 环境空气温度℃ Airtemperature℃C | 10 | 15 | 20 | 25 | 30 | 35 | 40 |
| 系数 Ratingfactors | 1.11 | 1.07 | 1.04 | 1.0 | 0.96 | 0.91 | 0.88 |
8.4注意事项:Mattersneedingattention
本样本提供的为交联聚乙烯系列电缆的载流量在特定安装条件的载流量,其他不同温度、土壤热阻条件下的载流量请参照换算系数进行换算。
The current-carrying capacity provided in this sample is for cross-linked polyethylene (XLPE) series cables under specific installation conditions.For other conditions with different temperaturesand soilthermal resistivity,please refer tothe conversion factors for calculation.
如需其他型号载流量,或特定安装条件下的载流量请咨询送公司技术服务中心,联系电话:。
For the current-carrying capacity of other models or under specific installation conditions,please consult the company's technical service center. Contact phone number: [phone number].
附录B:多组或成束敷设载流量降低系数 Appendix B: Current-carrying capacity derating factor for multi-group or bundled laying
电缆多组及成束敷设方式对载流量有很大的影响,特依据GB/T16895.6-2014建筑物电气装置第5-52部分:电气设备的选择和安装布线系统进行编制,作为选型设计参考,另需注意如下事项:
1、线缆束降低系数是基于束中所有导体长期稳态 100 % 负荷率运行,由于装置运行条件的变化,负荷率小于 100 % 时,则线缆束的降低系数可高一些。
2、电缆敷设的间距对载流量有较大影响,间距大时,降低系数可提高。
3、下列表中的线缆束降低系数是导体截面与敷设方式的平均值,实际偏差 < 5 % ,请设计选择时综合考虑,如敷设条件超出范围,请查阅标准GB/T16895.6-2014,或根据已知的条件进行计算;
The multiple groups and bundled laying methods of cables have a significant impact on the current carrying capacity.Therefore,according to GB/T16895.6-2014 Electrical installations of buildings Part 5-52: Selection and installation of electrical equipment and wiring systems,this document is compiled asa reference for selectionand design.Additionall,the following points should be noted: 1.The cable bundle reduction factor is based on the long-term steady-state 100 % load rate operation of all conductors in the bundle.Due tochanges in device operating conditions,when the load rate is less than 100 % . the reduction factor of the cable bundle can be higher.
2.The spacing of cable laying has asignificantimpact onthe current camying capacity,and when the spacing is large, the reduction factor can be increased.
3.Thecable bundle reduction factorin the following tableis the average value of conductor cross-section and laying method,with an actual deviation of less than 5 % Please consider it comprehensively when designing and selecting.If the laying conditions exceed the range,please refer to the standard GB/T 16895.6-2014,orcalculate based on known conditions;
表A-1 (Table A-1)
多回路或多根电缆成束敷设的降低系数
| 序号 Serial No. | 排列 (电缆相互接触) Arrangement(cables | 回路数或多芯电缆数量(Numberofcircuitsormulti-corecables) | ||||||||||
| 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 12 | 16 | 20 | ||
| inmutualcontact) 成束敷设在空气 中,沿墙、嵌入 或封闭式敷设 Bunchedinstallationin air,wallmounted, embeddedor | 一 1.00 0.80 | 0.70 | 0.65 | 0.60 | 0.57 | 0.54 | 0.52 | 0.50 | 0.45 | 0.41 | 0.38 | |
| 2 | enclosedlaying 单层敷设在墙上、 地板或无孔托盘上 Single-ayerlayingon wals,floors oropen cabletrays | 1.00 | 0.85 | 0.79 | 0.75 | 0.73 | 0.72 | 0.72 | 0.70 | 多于9个回路 或9根多芯电 缆不再减小 降低系数 No furtherderating factorreductionfor morethan9circuits | ||
| 3 | 单层直接固定在 天花板下 Fixedsinglelayer directlyunder ceing | 0.95 | 0.81 | 0.72 | 0.68 | 0.66 | 0.64 | 0.62 | 0.61 | |||
| 4 | 单层敷设在水平或 垂直的有孔托盘上 Sinizontarvyincan perforatedcabletrays | 1.00 | 0.88 | 0.82 | 0.77 | 0.75 | 0.73 | 0.72 | 0.72 | |||
| 5 | 单层敷设在梯架 或线夹上 Single-layerlayingon laddersorclamps | 1.00 | 0.87 | 0.82 | 0.80 | 0.80 | 0.79 | 0.78 | 0.78 | or9multi-corecables | ||
表A-2 (Table A-2)
多回路直埋电缆的降低系数 Derating factor for multi-circuit directly buried cables
| 回路数 Numbetrf | 电缆间的间距* (Spacingbetweencables*) | ||||
| 无间距(电缆相互接触) Noaspaincontact witheachother) | Outerieter of singlecable | 0.125m | 0.25m | 0.5m | |
| 2 | 0.75 | 0.80 | 0.85 | 0.90 | 0.90 |
| 3 | 0.65 | 0.70 | 0.75 | 0.80 | 0.85 |
| 4 | 0.60 | 0.60 | 0.70 | 0.75 | 0.80 |
| 5 | 0.55 | 0.55 | 0.65 | 0.70 | 0.80 |
| 6 | 0.50 | 0.55 | 0.60 | 0.70 | 0.80 |
| 7 | 0.45 | 0.51 | 0.59 | 0.67 | 0.76 |
| 8 | 0.43 | 0.48 | 0.57 | 0.65 | 0.75 |
| 9 | 0.41 | 0.46 | 0.55 | 0.63 | 0.74 |
| 12 | 0.36 | 0.42 | 0.51 | 0.59 | 0.71 |
| 16 | 0.32 | 0.38 | 0.47 | 0.56 | 0.68 |
| 20 | 0.29 | 0.35 | 0.44 | 0.53 | 0.66 |
表A-3 (TableA-3)
敷设在埋地管槽内多回路电缆的降低系数 Derating factor formulti-circuitcables laid inunderground ducts
| A)单路管槽内的多芯电缆(A)Multi-corecablesinsingleduct) | |||||
| 电缆根数 Numberof | 管槽之间距离* (Spacingbetween ducts*) | ||||
| Nospcng(mutuacontact) | 0.25m | 0.5m | 1.0m | ||
| 2 3 | 0.85 | 0.90 0.85 | 0.95 0.90 | 0.95 | |
| 0.75 | 0.80 | 0.85 | 0.95 | ||
| 4 5 | 0.70 | 0.80 | 0.85 | 0.90 0.90 | |
| 6 | 0.65 | 0.80 | 0.80 | 0.90 | |
| 7 | 0.60 0.57 | 0.76 0.80 | 0.88 | ||
| 8 | 0.54 | 0.78 | 0.88 | ||
| 9 | 0.52 | 0.74 0.77 | 0.87 | ||
| 10 | 0.49 | 0.73 0.72 | 0.76 | 0.86 | |
| 11 | 0.47 | 0.70 | 0.75 | ||
| 12 | 0.45 | 0.69 | 0.86 0.74 0.85 | ||
| B)非磁性单路管槽内的单芯电缆(B) Single-corecablesinnon-magneticsingleduct) | |||||
| 由两根或三根单芯 管槽之间距离* (Spacingbetweenconduits*) 电缆组成的回路数 | |||||
| singleumerof2/aicuis | Zzerosong(相econtact) 0.25m | 0.5m | |||
| 2 | 0.80 | 0.90 | |||
| 3 | 0.70 | 0.85 | |||
| 0.80 0.65 0.75 | 0.80 | ||||
| 4 5 | 0.70 | ||||
| 0.60 | |||||
| 6 | 0.60 | 0.70 | |||
| 7 | 0.53 | 0.66 0.76 | |||
| 8 | 0.50 | 0.74 | |||
| 9 | 0.63 0.47 0.61 | ||||
| 10 | 0.45 0.59 | 0.73 0.72 | |||
| 11 | |||||
| 12 | 0.43 0.57 0.41 0.56 | ||||
附录C
运输和贮存 Transportation and storage
电缆的运输和贮存应符合下列要求:
a)电缆应避免在露天存放,电缆盘不应平放;
b)运输中不应从高处扔下装有电缆的电缆盘,不应机械损伤电缆;
C)吊装包装件时,不应几盘同时吊装。在车辆、船舶等运输工具上,电缆盘应放置放稳,并用合适方法固定, 防止互撞或翻倒。
The transportation and storage of cables shall comply with the following requirements:
a) Cables should be avoided from being stored outdoors,and cable reels should not be laid flat; b) Cable reels containing cables should notbe dropped from high places during transportation, and cables should not be mechanically damaged;
c) When lifting packaging,several plates should not be lifted at the same time.On vehicles, ships,and other transportation vehicles,cable reels should be placed steadily and secured using appropriate methods to prevent collisions or tipping over.
电缆订购注意事项CableOrderingPrecautions
在进行电缆采购时,为了确保您能够获得符合项目需求的高质量产品,我们提醒您在表述采购需求时注意以下规范细节:
When purchasing cables,to ensure that you obtain high-quality products that meet the project requirements,we remind you to pay attention to the following standard details when expressingyour procurementneeds:
1.明确电缆型号:请根据电缆的用途和特性,准确指定电缆的型号。例如,若需要阻燃电缆,请明确标注“阻燃A类”(ZA)、“阻燃B类”(ZB)等。
Specify Cable Type: Please accurately designate the cable type based on its intended use and characteristics.For example,ifflame-retardantcablesare required,pleaseclearly indicate "Flame-retardant Class A" (ZA),“Flame-retardant Class B" (ZB),etc.
2.导体材料:请指明所需电缆的导体材料,如铜导体(T)或铝导体(L)、铝合金导体(LH)。若未特别指明,我们将默认提供铜导体电缆。
Conductor Material: Please specify the conductor material of the cable,such as copper conductor (T) or aluminum conductor (L)、Aluminum alloy conductor (LH) .If not specifically indicated,we will provide copper conductorcables bydefault.
3.绝缘和护套材料:请详细说明所需电缆的绝缘和护套材料,如聚氯乙烯绝缘(V)、交联聚乙烯绝缘(YJ)、聚氯乙烯护套(V)等。
Insulation and Sheath Materials:Please provide detailed information on the insulation and sheath materialsof the cable,such as polyvinyl chloride (Pvc) insulation (V),cross-linked polyethylene (XLPE) insulation (YJ), PVC sheath (V),etc.
4.铠装要求:若电缆需要铠装,请明确铠装类型,如双钢带铠装(2)、细圆钢丝铠装(3)等。
Armor Requirements: If armoring is required for the cable,please specify the type of armor, such as double steel tape armor (2),fine round steel wire armor (3),etc.
5.外护套:若电缆需要外护套,请指明外护套材料,如聚氯乙烯外护套(2)或聚乙烯外护套(3)。
Outer Sheath: If an outer sheath is needed for the cable,please indicate the material of thi outer sheath,such as PvC outer sheath (2) or polyethylene outer sheath (3)
6.尺寸规格:请提供电缆的标称截面积(如 1 . 5 \mathsf {mm } ^ { 2 } , 2 . 5 \mathsf {mm } ^ { 2 } 等)和长度要求。
Size Specifications: Please provide the nominal cross-sectional area of the cable (e.g., 1 . 5 \mathsf {mm } ^ { 2 } 2 . 5 \mathsf {mm } ^ { 2 } . )and the length requirements.
7.性能要求:请根据实际应用环境,指明电缆需要满足的性能标准,如耐温等级、耐压等级等。 Performance Requirements: Based on the actual application environment, please specify the performance standards that the cable needs to meet, such as temperature resistance level, voltageresistance level,etc.
8.特殊要求:若电缆有特殊应用需求,如阻水、耐油、耐酸碱、耐磨等,请在采购时明确说明。
Special Requirements: If the cable has special application requirements,such as waterblocking,oil resistance,acid and alkali resistance,wear resistance,etc.,please clearly state these requirements when purchasing.
9.数量和交货期:请提供所需电缆的数量和期望的交货期,以便我们更好地安排生产和物流。
Quantity and Delivery Schedule: Please provide the quantity of cables required and the desired delivery schedule so that we can better arrange production and logistics.
10.质量认证:请指明所需电缆是否需要通过特定的质量认证,如ISO认证、CCC认证等。请在采购订单中详细列明以上信息,以确保我们能够提供符合您需求的电缆产品。如有任何疑问,欢迎随时与我们联系。
Quality Certification: Please indicate whether the cables need to pass specific quality certifications,such as ISO certification,etc.Please list the above information in detail in the purchase order to ensure that we can provide you with the cable products that meet your requirements.If you have any questions,please feel free to contact us at any time.
传世界创未来
工程案例 PROJECT CASE